If you have ever sized a UPS, specified a transformer, or read a generator plate, you have met apparent power — the quantity rated in volt-amperes (VA) rather than watts. It is the number that determines how much current actually flows through cables and how much equipment capacity a load consumes, and it is almost never equal to the wattage on the same label. This converter handles the four units it comes in — millivolt-amperes (mVA), volt-amperes (VA), kilovolt-amperes (kVA), and megavolt-amperes (MVA) — in one step. Enter a value, pick its unit, and all four conversions refresh live as you type.
Everything runs locally in your browser: free, no signup, nothing transmitted. It works on a phone, which suits the moment this tool gets used — standing in front of a transformer nameplate or comparing UPS datasheets with a vendor on a call.
The four-at-once display matters because sizing conversations jump scales constantly. A server rack draws 4.6 kVA; the data room's upstream panel is rated 250 kVA; the utility feeds the building through a 1.5 MVA transformer. All three numbers must line up in one capacity chain, and this tool keeps the arithmetic out of the conversation.
VA Versus Watts: The Quantity That Actually Limits Equipment
Apparent power (S) is simply voltage times current: S = V × I, measured in volt-amperes. Real power (P) is the portion that does work, measured in watts. In an AC system they differ whenever voltage and current are out of step — the defining property of inductive loads like motors and transformers, or electronic loads with distorted current. The ratio between them is the power factor: pf = P / S.
Here is why VA, not watts, sizes equipment. A 1,000 W load at a power factor of 0.8 draws 1,250 VA — 1,250 volt-amperes of current-carrying demand. The extra 250 VA does no useful work, but the current is real, so the wire, breaker, transformer winding, and UPS inverter all must carry it. Equipment is rated by current and thermal capacity, which track VA. That is why UPS units say 1,500 VA, transformers say 75 kVA, and generators say 40 kVA: those ratings describe what the hardware can physically supply, independent of what the load does with it.
The three quantities form the power triangle: S² = P² + Q², where Q is reactive power in var. A load at exactly 1.0 power factor — a heater, a kettle — has VA equal to watts. Most real facilities sit between 0.75 and 0.95.
What Units Does This Converter Handle?
- Millivolt-amperes (mVA). One thousandth of a VA. Small electronics, individual power supplies, instrument transformers' secondary burdens.
- Volt-amperes (VA). The base unit here. Desktop UPS units (typically 500–1,500 VA), wall adapters, and single devices.
- Kilovolt-amperes (kVA). One thousand VA. The workhorse unit: facility panels (250 kVA), distribution transformers (25–2,500 kVA), commercial generators (30–2,000 kVA).
- Megavolt-amperes (MVA). One thousand kVA. Substation transformers (10–500 MVA), power plant ratings, and utility interconnection studies.
The prefixes are exact decimal steps: 1 kVA = 1,000 VA = 1,000,000 mVA, and 1 MVA = 1,000 kVA. There are no physical conversion factors — unlike horsepower, all four are the same unit at different scales, so conversions are exact with zero rounding.
How to Use This Converter (Step by Step)
- Type the apparent power value you have — 1,500, 75, 0.5, or any decimal.
- Select its unit: mVA, VA, kVA, or MVA.
- Read all four results, refreshed on every keystroke.
- Change the value or unit for the next sizing check.
Worked example one: enter 1,500 and choose VA, a common desktop UPS rating. The results are 1.5 kVA, 1,500,000 mVA, and 0.0015 MVA — and at a 0.9 power factor, that UPS delivers 1,350 W of real power. Worked example two: enter 0.5 and choose MVA, a pad-mount distribution transformer. The results are 500 kVA, 500,000 VA, and 500,000,000 mVA; at 0.95 facility power factor it supports 475 kW of load.
How It Works: The Conversion Factors and the Power Triangle
1 kVA = 1,000 VA = 1,000,000 mVA1 MVA = 1,000 kVA = 1,000,000 VAP (W) = S (VA) × power factorQ (var) = S × sin(acos(pf))
Internally, the input is normalized to a base value in VA and the other three results derive from that single base. The interesting arithmetic is the triangle, not the prefixes. Worked example: a facility draws 400 kW at a power factor of 0.80. Apparent power is 400 / 0.80 = 500 kVA, and reactive power is the square root of 500² − 400² = 300 kvar. If the power factor improves to 0.95, the same 400 kW needs only 421 kVA — the transformer headroom appears without any new hardware.
Reference Table: Common Ratings in All Four Units
| Rating | mVA | VA | kVA | MVA |
|---|---|---|---|---|
| Laptop power adapter (90 VA) | 90,000 | 90 | 0.09 | 0.00009 |
| Desktop UPS (1,500 VA) | 1,500,000 | 1,500 | 1.5 | 0.0015 |
| Small business generator (30 kVA) | 30,000,000 | 30,000 | 30 | 0.03 |
| Pole transformer (50 kVA) | 50,000,000 | 50,000 | 50 | 0.05 |
| Substation transformer (60 MVA) | 60,000,000,000 | 60,000,000 | 60,000 | 60 |
Two anchors worth memorizing: a 1 kVA rating is 1,000 VA, and at a typical 0.8 power factor that same rating delivers about 800 W of usable real power. The second number is what a load will actually consume; the first is what the supply must be able to push.
Common Use Cases
- UPS sizing. Add up the VA of everything the UPS must support — a workstation at 300 VA, a monitor at 40 VA, a network switch at 30 VA — then keep 20–25% headroom below the rating. A 1,500 VA UPS realistically supports about 1,350 W at pf 0.9, so a 1,200 W load chain fits with margin.
- Transformer selection. Diversity rules apply — a 50 kVA pole transformer serves four houses that individually peak near 15 kVA because their peaks do not coincide. Converting between VA, kVA, and MVA is the daily arithmetic of distribution planning.
- Generator specification. A 100 kVA generator at 0.8 pf delivers 80 kW. If the connected load is 90 kW of motors, 100 kVA is not enough even though "90 kW sounds less than 100 kVA" — the triangle decides.
- Data center capacity chains. Racks (5–15 kVA each) feed rows (150–400 kVA) that feed rooms (1–3 MVA). The units must reconcile at every level for the chain to be credible.
- Utility demand charges. Many tariffs bill on kVA demand rather than kW, so a facility with a poor power factor pays for the gap — the space between 400 kW and 500 kVA in the example above.
Tips and Best Practices
- Never assume pf = 1. Marketing copy sometimes quotes UPS "watts" that are really VA, or quotes both without naming the power factor used. The safe habit is to ask what pf the vendor assumed; ratings at 0.9 flatter the same hardware that older spec sheets rated at 0.8.
- Leave real headroom. Sizing a UPS or transformer at exactly the computed load leaves nothing for inrush, growth, or measurement error. 20–25% margin is the standard engineering cushion.
- Do not add VA blindly across different power factors. Adding 500 VA of heater (pf 1.0) and 500 VA of motor (pf 0.7) gives 1,000 VA of apparent load, but the kW total is only 500 + 350 = 850 W. Apparent power adds; real power also adds; the mixture's power factor shifts, and you must recompute the triangle for the combined load.
- Check the input voltage. The same 1,500 VA rating means 12.5 A at 120 V but 6.25 A at 240 V. VA is voltage-independent, amps are not — this trips people converting US equipment to European supplies.
- Watch case conventions. mVA and MVA differ by nine orders of magnitude. If a "1.5" produces absurd results, the unit selector is the first suspect.
Limitations and Honest Caveats
This tool converts among units of apparent power — a magnitude computed from voltage and current. It does not measure anything, does not apply power factor to turn VA into watts (that is your input to provide), and does not handle reactive power (var) or real power (W) directly, though the formulas above connect all three. It does not model harmonics: electronic loads with distorted current waveforms can need more VA than the simple V × I picture suggests, which is why K-factor and derating tables exist for transformer selection. For exact conversion among mVA, VA, kVA, and MVA, it is complete.
Why the VA Rating Exists at All
It would be simpler if everything were rated in watts, but watts understate what equipment must physically handle. A transformer winding heats according to current, a UPS inverter switches according to current, and current follows VA — not the useful subset of VA. Rating in VA is the hardware manufacturer being honest about thermal and magnetic limits, just as rating a truck in payload rather than cargo value is being honest about what the axles carry. Once you internalize the triangle — watts times power factor is VA, and VA is what the wire feels — the whole vocabulary of UPS sizing, transformer selection, and demand charges falls into place. This converter keeps the four scales of that vocabulary in one view: enter any value in mVA, VA, kVA, or MVA and the rest appear instantly, computed locally with exact decimal factors.