🌀

Reactive Power Converter

✓ Free & no signup 🔒 Runs 100% in your browser Updated 2026-11-25 Unit Converter Tools
—
Millivars
—
VARS
—
Kilovars
—
Megavars

Reactive power is the least visible quantity on an electrical bill, yet industrial facilities are charged real money for it. When motors, transformers, and other inductive equipment run, they draw current that oscillates back and forth between the source and the load's magnetic fields without being consumed — that back-and-forth flow is reactive power, measured in volt-amperes reactive (var). This converter handles the four units it comes in — millivolt-amperes reactive (mvar), volt-amperes reactive (var), kilovolt-amperes reactive (kvar), and megavolt-amperes reactive (Mvar) — in one step. Enter a value, pick its unit, and all four conversions refresh live as you type.

The tool runs entirely in your browser: free, no signup, no data leaves your device. It works on mobile, so a facilities engineer can check a capacitor-bank specification from the plant floor.

Showing all four units at once matches how the field actually communicates. A single motor starter might have a 2 kvar snubber capacitor; the plant's correction bank is rated 150 kvar; a utility interconnection agreement specifies 10 Mvar of grid support. These are the same physical quantity at three scales, and this tool keeps them in one view so nobody rescales by hand.

What Is Reactive Power, Really?

Picture a piston compressor: energy goes into compressing air during one stroke and comes back out on the return, doing no net work on the world beyond friction. An induction motor's magnetizing current behaves similarly in the electrical sense. On each AC cycle, current flows into the motor's windings to build a magnetic field, then returns to the grid as the field collapses. The energy is borrowed and repaid twice per cycle, 120 times a second on a 60 Hz system, and it never turns into heat, light, or torque.

That borrowed flow is reactive power (Q). It is real current through real wires, so it heats cables, trips breakers, and consumes transformer capacity — it just does no useful work. Total current in the wires is set by apparent power (S, in VA), the vector sum of real power (P, in W) and reactive power (Q, in var). The three form the classic power triangle, linked by S² = P² + Q² and cos φ = P / S, where φ is the phase angle between voltage and current and cos φ is the power factor.

A purely resistive load — a heater, an incandescent bulb — draws no reactive power; its power factor is 1.0. An induction motor running at partial load can have a power factor of 0.7 or lower, meaning 30% of the current it pulls is magnetizing current. That gap between what you use and what you draw is what utilities police, and what capacitor banks exist to fix.

What Units Does This Converter Handle?

  • Millivolt-amperes reactive (mvar). One thousandth of a var. Small control circuits, instrument-level inductive loads, and individual sensor coils.
  • Volt-amperes reactive (var). The base unit here. Small motor loads, single lighting ballasts, component-level magnetics.
  • Kilovolt-amperes reactive (kvar). One thousand vars. The everyday industrial unit: motor banks, capacitor stages (typically 25–100 kvar each), panel-level correction.
  • Megavolt-amperes reactive (Mvar). One thousand kvar. Utility and grid scale: synchronous condensers, STATCOMs, substation shunt reactors rated tens to hundreds of Mvar.

The prefixes are exact decimal steps: 1 kvar = 1,000 var = 1,000,000 mvar, and 1 Mvar = 1,000 kvar.

How to Use This Converter (Step by Step)

  1. Type the reactive power value you have — 50, 250, 10, or a decimal like 0.75.
  2. Select its unit: mvar, var, kvar, or Mvar.
  3. Read all four results, updated on every keystroke with no button to press.
  4. Change the value or unit for the next conversion.

Worked example one: enter 150 and choose kvar, a mid-size correction bank. The results are 150,000 var, 150,000,000 mvar, and 0.15 Mvar. Worked example two: enter 0.5 and choose Mvar, one stage of a substation compensation system. The results are 500 kvar, 500,000 var, and 500,000,000 mvar.

How It Works: The Conversion Factors

  • 1 kvar = 1,000 var = 1,000 mvar × 1,000
  • 1 Mvar = 1,000 kvar = 1,000,000 var
  • 1 var = 1,000 mvar

Internally, the input is normalized to a base value in var and the other three results derive from that single base, so the set stays mutually consistent. There are no unit-specific physical factors here — unlike horsepower, all four are the same unit with decimal prefixes — so the conversion is exact with no rounding to hide.

Where the arithmetic gets interesting is the power triangle, not the prefixes. Worked example: a plant draws 800 kW of real power at a power factor of 0.75. Apparent power is 800 / 0.75 = 1,066.7 kVA, and reactive power is the square root of 1,066.7² − 800² = 705.5 kvar. Correcting to a power factor of 0.95 requires about 443 kvar of capacitance, which the utility will typically credit on the demand charge.

Reference Table: One Unit Expressed in All Four

FrommvarvarkvarMvar
1 mvar10.0010.0000010.000000001
1 var1,00010.0010.000001
1 kvar1,000,0001,00010.001
1 Mvar1,000,000,0001,000,0001,0001

Real-world anchors: a 2 kvar capacitor stage protects a small motor starter; a 25 kvar stage is the workhorse of industrial correction; a mid-size HVAC chiller plant needs a 150–400 kvar bank; and a large synchronous condenser provides ±250 Mvar of grid support.

Common Use Cases

  • Capacitor bank sizing. The standard fix for poor power factor is adding capacitance equal to the inductive kvar you want to cancel. Sizing means computing the kvar difference between the present and target power factor — a pure kvar calculation from start to finish.
  • Utility demand-charge review. Many tariffs bill kVA demand or penalize power factor below 0.90–0.95. Translating a meter reading of 705.5 kvar into the plant's kW context shows whether correction pays for itself in months.
  • Motor and transformer documentation. Nameplates and datasheets quote magnetizing vars at various loads; comparing a 2 kvar motor figure against a 100 kvar panel budget requires the unit bridge this tool provides.
  • Grid and renewable interconnection. Inverter-based solar and wind plants are specified for reactive capability, often as ±0.33 Mvar per 1 MW of inverter capacity; interconnection studies communicate in Mvar.
  • HVAC and pump systems. Large chillers, compressors, and variable-speed drive installations dominate a facility's reactive load; knowing their combined kvar is the first step of any efficiency audit.

Tips and Best Practices

  • Do not add kvar and kW. They are perpendicular components, not addable numbers: 800 kW plus 705.5 kvar is not 1,505.5 of anything. The vector sum is apparent power, 1,066.7 kVA in that example. Only apparent power adds arithmetically to a cable's ampacity question.
  • Capacitors are fixed; loads are not. Overcorrecting at light load raises voltage and can push the power factor leading. Automatic banks switch stages (25 kvar, then 50 kvar more) to track the load, which is why stage ratings are quoted in kvar.
  • Harmonics change the picture. Variable-speed drives inject harmonic current that plain capacitors can amplify. Serious correction projects measure the harmonic spectrum first — the kvar figure alone does not capture resonance risk.
  • Check which var convention the document uses. Lagging vars (inductive) and leading vars (capacitive) have opposite signs in some conventions. Magnitudes convert the same; the engineering sign depends on context.
  • Sanity anchors. A household appliance draws a few var at most; an office building 50–200 kvar; a steel mill 10–50 Mvar of historic magnetizing demand. If a result lands an order of magnitude off, re-check the selected unit.

Limitations and Honest Caveats

This tool converts among units of reactive power — a magnitude, not a signed or phase-resolved quantity. It does not compute the power triangle for you (you need kW and power factor, or kVA and kvar, as inputs), does not model harmonics or flicker, and does not handle reactive energy (varh), which is reactive power integrated over time and belongs to a different converter. It also will not tell you whether a 0.75 power factor is acceptable under your specific tariff; that is a contract question. For exact conversion among mvar, var, kvar, and Mvar, it is complete.

Why Utilities Care So Much About kvar

A utility cannot bill borrowed energy twice — the magnetizing current returns to the grid each cycle. But the utility still pays to carry it: generation, transformers, and conductors must be sized for apparent power, not real power. That is why tariffs measure demand in kVA or kvar, why industrial customers install correction banks, and why grid operators buy Mvar of support from synchronous condensers and inverter plants. Reactive power is invisible on a wall meter but decisive in infrastructure economics. This converter speaks all four of its scales at once — enter any value in mvar, var, kvar, or Mvar and the rest appear instantly, computed locally in your browser with exact decimal factors.

Frequently Asked Questions

What is reactive power in simple terms?
Reactive power is electrical energy that sloshes back and forth between the grid and a load's magnetic fields instead of being consumed. Inductive equipment like motors and transformers borrows current each AC cycle to build a magnetic field, then returns it as the field collapses — no net energy is used, but real current still flows through real wires. It is measured in volt-amperes reactive (var) to distinguish it from watts, which measure power that actually does work. Reactive power heats cables and fills transformer capacity, which is why utilities track it even though it is not consumed.
What is the difference between kW and kvar?
Kilowatts (kW) measure real power — energy actually converted into work, heat, or light. Kilovolt-amperes reactive (kvar) measure reactive power — the magnetizing flow that oscillates without doing work. They are two perpendicular components of apparent power (kVA), related by S² = P² + Q². A plant drawing 800 kW at 0.75 power factor also draws about 705.5 kvar, and its apparent power is 800 / 0.75 = 1,067 kVA. You cannot add kW and kvar directly; they combine as vector components. Utilities bill for kW but often penalize or demand-charge on kvar or kVA.
How do you calculate the kvar needed for power factor correction?
First find your present reactive power: kvar = kW × tan(acos(pf)). For 800 kW at 0.75 power factor, that is 800 × 0.8819 ≈ 705.5 kvar. Then compute the target: at 0.95, 800 × tan(acos(0.95)) ≈ 800 × 0.3287 ≈ 263 kvar. The correction capacitance needed is the difference, about 443 kvar. In practice, engineers use manufacturer tables listing kvar per kW for each pf-from-to pair, then select standard capacitor stages (typically 25–100 kvar each) with automatic switching to track load changes.
How many vars are in a kvar?
Exactly 1,000. The prefix kilo- means one thousand, so 1 kvar = 1,000 var and 1 var = 0.001 kvar. Continuing the chain, 1 kvar is also 1,000,000 mvar and 0.001 Mvar. To convert kvar to var, multiply by 1,000: a 150 kvar capacitor bank is 150,000 var. To convert var to kvar, divide by 1,000. Enter either value in the converter and all four scales — mvar, var, kvar, Mvar — appear at once, since the units differ only by decimal prefixes with no rounding involved.
Why do utilities charge for reactive power?
Because the infrastructure must carry it even though it is not consumed. Wires, transformers, and generators are sized for total current — apparent power — not just the useful portion. A customer drawing 800 kW at 0.70 power factor forces the utility to supply roughly 1,143 kVA of capacity to deliver 800 kW of real work. To recover that cost and free up grid capacity, tariffs add kVA demand charges or power-factor penalties, typically triggering below 0.90–0.95. Industrial customers respond with capacitor banks, which supply reactive power locally and can pay for themselves within one to three years.
What is a Mvar and where is it used?
A Mvar is one megavolt-ampere reactive — 1,000 kvar or 1,000,000 var. It is the unit of grid-scale reactive power: transmission operators quote voltage support in Mvar, synchronous condensers provide ±100 to ±300 Mvar, and static compensators (STATCOMs) ramp tens of Mvar in milliseconds. Large solar and wind interconnection agreements require reactive capability often quoted around ±0.33 Mvar per MW of inverter capacity. Shunt reactors on long cables absorb Mvar to keep voltage from rising. Entering a Mvar value in the converter shows its kvar, var, and mvar equivalents instantly.

Related Tools